The Digital Controller For Multiscroll Chillers ESIE06-05
2–36 Part 2 – Functional Description
3
1
2
4
5
Free Cooling
Ambient
This screen allows modification of the free cooling based on ambient temperature.
Settings:
Free Cooling Inlet-
Ambient
This screen allows modification of the free cooling, based on the difference between inlet water
temperature and ambient temperature.
Settings:
Remark: During free cooling, based on inlet-ambient, the pump contact is always closed.
MODE : AMBIENT, free cooling based on ambient temperature
SP : Define setpoint of free cooling
DIF : Setting of the free cooling difference
PUMP : Define if pump is ON/ OFF during free cooling operation
LEAD : Lead time of the evaporator water pump
FREE COOLING_
MODE:AMBIENT
SP: 05.0 °C DIF:01.0 °C
PUMP:ON LEAD:000s
MODE : INLET-AMBIENT, free cooling based on the difference between inlet water
temperature and ambient temperature
SP : Define setpoint of the free cooling
DIF : Setting of the free cooling difference
FREE COOLING_
MODE:INLET-AMBIENT
SP:05.0 °C DIF:050.0 °C