Daikin EWYQ230DAYN [298/524] Cool eev control

Daikin EWYQ230DAYN [298/524] Cool eev control
The Digital Controller For Multiscroll Chillers ESIE06-05
2–72 Part 2 – Functional Description
3
1
2
4
5
EEV Normal Feed
Forward Control
This screen allows modification of the EEV FF control in cooling mode.
Settings:
EEV Low Ambient
Feed Forward
Control
This screen allows modification of the EEV FF control in cooling mode with low ambient temperatures.
Settings:
FF CONTROL UP : If the compressor load goes up, the controller will change the EEV
opening.
Output pulses= Current pulses x “FF CONTROL UP”
FF CONTROL DOWN : If the compressor load goes down, the controller will change the
EEV opening.
Output pulses= Current pulses / “FF CONTROL DOWN”
_
FF NORMAL UP:1.3
FF NORMAL DOWN:1.5
COOL EEV CONTROL
FF LOW AMB. UP : If the compressor load goes up AND the ambient temperature is
below the COOL AMB. CONST setpoint, the controller will change
the EEV opening.
Output pulses= Current pulses x “FF LOW AMB. UP”
FF LOW AMB. DOWN : If the compressor load goes down AND the ambient temperature
is below the COOL AMB. CONST setpoint, the controller will
change the EEV opening.
Output pulses= Current pulses / “FF LOW AMB. DOWN”
_
FF LOW AMB.UP :1.1
FF LOW AMB.DOWN:1.2
COOL EEV CONTROL