The Digital Controller For Multiscroll Chillers ESIE06-05
2–74 Part 2 – Functional Description
3
1
2
4
5
Superheat Limits or
C1 in Cooling
This screen allows modification of the upper and lower limit of the suction superheat of circuit 1 in
cooling mode.
Settings:
Remark: The suction super heat target changes according to the discharge super heat. However, this
between an upper and lower superheat limit.
Superheat Limits of
C1 in Heating
This screen allows modification of the upper and lower limit of the suction superheat of circuit 1 in
heating mode.
Settings:
Remark: The suction super heat target changes according to the discharge super heat. However, this
between an upper and lower superheat limit.
C1 SH L LIM COOL : Superheat lower limit in cooling mode for circuit 1
C1 SH U LIM COOL : Superheat upper limit in cooling mode for circuit 1
_
C1SH U LIM COOL:08.5 °C
C1SH L LIM COOL:04.0 °C
EEV CONTROL
C1 SH L LIM HEAT : Superheat lower limit in heating mode for circuit 1
C1 SH U LIM HEAT : Superheat upper limit in heating mode for circuit 1
_
C1SH U LIM HEAT:08.0 °C
C1SH L LIM HEAT:03.0 °C
EEV CONTROL