Daikin EWYQ230DAYN [326/524] Start eev 0200pls

Daikin EWYQ230DAYN [326/524] Start eev 0200pls
The Digital Controller For Multiscroll Chillers ESIE06-05
2–100 Part 2 – Functional Description
3
1
2
4
5
This screen allows modification of the defrost parameters.
Settings:
This screen allows modification of the defrost stop conditions.
Settings:
START EEV : Start opening of the EEV by switching from heating to cooling
mode during the defrost cycle.
START KEEP TME : Time when the START EEV pulses are used before normal
cooling EEV control is active.
RESET COIL TEMP : Stop condition of the defrost cycle based on the coil
temperature.
_ DEFROST
START EEV:0200pls
START KEEP TIME:005s
RESET COIL TEMP:20°C
RESET SET PR : Stop condition of the defrost cycle based on the high pressure.
RESET OUTL TEMP : Stop condition of the defrost cycle based on the outlet water
temperature.
_ DEFROST
START EEV:0200pls
START KEEP TIME:005s
RESET COIL TEMP:20°C