ESIE06-05 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–141
3
2
4
5
1
3.13 Changeable digital outputs
Introduction 6 changeable digital outputs are available and can be assigned to 20 different functions in the service
menu.
Function overview Possible settings for changeable digital outputs
When NONE (OPEN) is selected.
-The digital output will open.
When Close is selected:
- The digital output will close.
When 2ND PUMP is selected:
- The digital output will indicate (close) the status of the second pump.
When 100% capacity is selected:
- The digital output will indicate (close) when the unit is working at 100 percent capacity.
When FULL CAPACITY is selected:
- The digital output will indicate (close) when the unit is working at maximum capacity, example
reached 100% capacity or reached maximum capacity because of safety limitation.
When FREE COOLING is selected:
- The digital output will close when the free cooling mode is active.
When GENERAL OPERATION is selected:
-The digital output will indicate (close) when the unit is active.
When SAFETY+W(NO) is selected
-The digital output will indicate (close) when a safety or warning is active. (Normal open contact)
When SAFETY+W(NC) is selected:
-The digital output will indicate (close) when a safety or warning is active. (normal closed contact)
When SAFETY (NO) is selected:
- The digital output will indicate (close) when a safety is active (normal open contact).
When SAFETY (NC) is selected:
-The digital output will indicate (close) when a safety is active (normal closed contact).
When C1 or C2 SAFETY is selected:
-The digital output will indicate (close) when a safety is active for the specified circuit.
When WARNING is selected:
-The digital output will indicate (close) when a warning is active.
When C1 or C2 OPERATION is selected:
- The digital output will indicate (close) when the specified circuit is active.
When COOLING or HEATING or DEFROST is selected:
- The digital output will indicate (close) when the unit is in Cooling/Heating or Defrost.
When 0% CAPACITY is selected:
-The digital output will indicate (close) when the unit capacity is 0%