Daikin EWYQ230DAYN [256/524] All fans off

Daikin EWYQ180DAYN [256/524] All fans off
The Digital Controller For Multiscroll Chillers ESIE06-05
2–30 Part 2 – Functional Description
3
1
2
4
5
This screen allows modification of the start and stop time of the fan low noise mode.
This screen is only visible when “DAILY SCHEDULE” is selected as fan low noise mode.
Settings:
Fan forced ON This screen allows modification of the fan forced ON function.
Possible settings :
START : start time of the low noise mode
STOP : stop time of the low noise mode
FAN LOW NOISE_v
MODE:DAILY SCHEDULE
START:20h00
STOP:06h00
OFF :
If the unit is OFF, then all the fans are OFF.
ON : If the unit is OFF, then all the fans are ON.
CH. DIG. INP. : If the unit is OFF, all the fans can be switched on by use of a
changeable digital input, programmed in the service/fan
menu (Fan Forced ON).
FAN FORCED ON_
IF UNIT IS OFF THEN
ALL FANS:OFF