The Digital Controller For Multiscroll Chillers ESIE06-05
2–94 Part 2 – Functional Description
3
1
2
4
5
LP Setpoint and
Mask Timers
This screen allows modification of the low pressure alarm setpoint and the low pressure mask timers.
Settings:
Freeze-up Settings This screen allows modification of the freeze-up safety settings.
Settings:
LP SETPOINT:
If the low pressure drops below the LP setpoint
stop the unit immediately on LP Error.
Cooling mode: 1,2 bar
Heating mode: 0,5 bar
FAN LP MASK: Mask time of 30sec from fan switching (only fan Load up)
COMPR LP MASK: Mask time of 30sec from 1st compressor start-up (no masking at 2nd
compressor start)
_ SAFETY
LP SETP. C:1.2b H:0.5b
FAN LP MASK:030s
COMPR LP MASK:030s
FREEZE UP DIS:
Freeze-up disabling setpoint, used for:
Freeze-up protection = FREEZE UP DIS setpoint
Freeze-up Prevention = FREEZE UP DIS setpoint +0,5°C
RESET:
Reset value of freeze-up prevention / protection
Freeze-up protection : Above RESET value, possible to reset freeze-up safety
Freeze-up prevention : Above RESET value, back to normal thermostat control
_ FREEZE UP SAFETY
FREEZE UP DIS:004.0 °C
RESET:005.0 °C