Daikin EWYQ230DAYN [330/524] 104 part 2 functional description

Daikin EWAQ180DAYN [330/524] 104 part 2 functional description
The Digital Controller For Multiscroll Chillers ESIE06-05
2–104 Part 2 – Functional Description
3
1
2
4
5
DICN
_v
DICN SETTING
MS OPTION:N
UNIT:MASTER
NR OF SLAVES:1
DICN SETTING
ADD SL1:---
_÷ MASTER SETTING
PRIORITY:0-2
STEPLENGTH:1.5¢
STANDBY IF MAX CAP:Y
_^ DICN THERMOSTAT
STEPLENGTH
A:04.0¢ B:03.2¢ C:00.4¢
COMMUNICATION
_v
COMMUNICATION
EXT. PCB:4SSR+HIC
COMM. PCB:DIII+SER
COMM.P1P2 PCB:NONE
_÷ COMMUNICATION PCB
EEV. PCB:UNI POLAR
_÷ COMMUNICATION PCB
RS232:NONE
BR:19200bps
_÷ COMMUNICATION PCB
RS485:NONE ADDR:01
BR: 19200bps
PARITY:NONE (2STOPb)
_÷ COMMUNICATION PCB
DIII:YES
ADDR:--- POWER:Y
AIRNET:01 AUTO:Y
_^ COMMUNICATION
BMSCONTROL ALLOWED:N
SAFETY
_v
SAFETY
MIN.OUTL.WATER:004.0¢
IF NO FLOW AFTER
PUMPLEADTIME:ALARM
SAFETY
HPSETB:37.4b DIFF:0.4b
MASK INVFAN SAF:120s
SAFETY
PASSWORD NEEDED TO
RESET SAFETIES:
NONE
SAFETY
FAN OVERC.:WARNING
SAFETY
IF UNITSAFETY THEN
PUT UNIT OFF: NO
SAFETY
HIGH DIS SAFETY:135¢
SAFETY
LP SETP. C:1.2b H:0.5b
FAN LP MASK:030s
COMPR LP MASK:030s
_÷ FREEZE UP SAFETY
FREEZE UP DIS:003.0¢
RESET:004.0¢
PUMP ON SETP.:001.5¢
REFR TEMP SET:-03.5¢
_÷ FREEZE UP SAFETY
START CONTROL:110¢
STOP CONTROL:109¢
RESET TO NORMAL:090¢
_÷ DISCH GAS SAFETY _÷ DISCH GAS SAFETY _^ RESTART SAFETY
GRD:03m AREC:005m
RESTART POWERON:030s
REF GRD EXTEND:12m
CONTROL EEV:001pls
ADVANCED
_v
ADVANCED
AUTORESTART :YES
_^ ADVANCED
SIMULATION:NO
AI:0
EEV:0
HISTORY
_
HISTORY
EXTRA SCREENS:N
DEFROST
_v
DEFROST
START CONST TEMP:10¢
NORMAL TIMER:030m
SHORT TIMER: 10m
DEFROST
LEAD TIME:030s
DEFROST
START EEV:0200pls
START KEEP TIME:005s
RESET COIL TEMP:120¢
DEFROST
RESET SET PR.:25.0b
RESET OUTL TEMP:04¢
_^
DEFROST
INITIAL EEV:0200pls
INITIAL TIME:030s
EEV KEEP TIME:030s