Daikin EWYQ230DAYN [459/524] Procedure to clear the refrigerant circuit in case of frozen evaporators

Daikin EWAQ080DAYN [459/524] Procedure to clear the refrigerant circuit in case of frozen evaporators
ESIE06-05 Procedure to Clear the Refrigerant Circuit in Case of Frozen Evaporators
Part 3 – Troubleshooting 3–59
33
4
5
1
Part 3
12 Procedure to Clear the Refrigerant Circuit in Case of
Frozen Evaporators
If water is detected in the refrigerant circuit after a evaporator damage, the following procedure should
be executed to clear the system.
Step Action
1 Cleaning & drying refrigerant circuit.
Cleaning components:
Suction and liquid line.
Replace components:
Sight glass
Drier filter element by high density filter
Compressor oil
Actions:
Drill a hole in the bottom of the condenser headers to remove
water.
Braze the drilled holes.
Blow dry N2 trough all the pipes.
Drain compressor oil
Vacuum the whole installation:
Check on a regular base the condition of the oil of the vacuum
pump. If the vacuum oil becomes milky, it should be replaced by
new vacuum oil. The crankcase heater must be activated. It is
advisable to connect a second heater tape at the suction of the
compressor.
Stop the vacuum and purge with dry nitrogen.
Restart the vacuum of the installation; check after a couple of
hours the condition of the vacuum oil. If OK the unit can be
recharged.
Charge the unit with R410A.
Start the unit & re-commissioning.
After 24 hours replace HD filter by new HD filter & replace
compressor oil.
Check oil contamination with measuring kit.
After 48 hours replace HD filter by normal filter drier + check sight
glass and pressures.
2 Find the cause of this evaporator breakdown and take the necessary
actions to prevent recurrence in the future.