ESIE06-05 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–121
3
2
4
5
1
1 : Ambient setpoint A
2 : 1 + 2°C
3: Ambient Setpoint B
4: 3 + 2 °C
Parameter 1 and 3 can be changed in the service/fan menu.
Fan control based
on high pressure
with inverter fans
High pressure based control for inverter fans.
After the first 70 seconds (default) fan control is based on high pressure value.
Remark:
There are different switching points for fan up depending if 1 or 2 compressors are running in that
circuit.
Low
-15°C
-13°C
-10°C
-8°C
-5°C
-3°C
5°C
7°C
15°C
17°C
High
20/13%
20/20%
30/30%
30/33%
50/53%
100%/100%
Ambient temperature
Unit with 8 fanstep
Unit with 12 fanstep
Fanstep
100%
95%
Step
Down
Step
Up
30%
20%
A: 18,9 bar B2:27,5bar
B2 (50%):
24,9 bar
2,6bar
B3: 35 bar
Min. time
between
UP& UP:
10sec
Min. time
between
UP& UP:
15sec
Min. time
between
DWN& DWN:
90sec
In case 1 comp or
no compr running
High pressure