Daikin EWYQ230DAYN Сервис мануал онлайн [350/524] 403923

Daikin EWYQ230DAYN Сервис мануал онлайн [350/524] 403923
Functional Control for a Standalone Unit ESIE06-05
2–124 Part 2 – Functional Description
3
1
2
4
5
When a fanstep down is executed by the pressure diff surveillance control, then fanstep up is not
allowed unless one of following conditions is met:
Unit stop/Thermo off
1.5 hr after start of this forbidden area.
Water temp. drop : -2°C (bigger pressure difference due to LP drop).
Rise of outdoor temp.: +3 °C or more (bigger pressure difference due to HP rise).
Fan control in
heating mode
Fan management : heating mode
Fanstep = 100 % (step)
Fanstep = 100 % (inverter fans)
Fan output for
inverter fans
Fanstep output for 50-60Hp units
Fanstep output for 70-80Hp units
OFF
20
1
OFF
302
OFF
45
3
OFF
504
ON
ON
ON
ON
20Hz
705
30Hz
80
6
45Hz
957
50Hz
20Hz
30Hz
45Hz
50Hz
1008
%
K14F
K24F
K13F
K23F
Fanstep
Changeover
on/off fan &
Fan inv