Procedure for Software Upload ESIE06-05
3–38 Part 3 – Troubleshooting
3
1
3
4
5
6. Push Start
(Remark: default password is 0000 and
must not be modified)
Result:
A pop-up window will show progress and progress is
recorded in logging-area. During upload:
MainRemocon display: “-PCB SW UPLOAD
BUSY-”
SubRemocon display: “-PCB SW UPLOAD
BUSY-” (if present)
Result should be OK at the end. (Remark: Upload by
PCASOflash can take up to +- 4 min.) (Remark: if
result is OK, then communication cable can be
removed)
If uploading ended correctly
then Main PCB nr 1 will automatically distribute
software towards Main PCB nr 2 (if present)
MainRemocon display “----STARTUP BUSY----“
SubRemocon display “----STARTUP BUSY----“ (if
present)
After this Main PCB nr 1 will automatically distribute
software towards Remocon PCB Main (if present):
MainRemocon display “-REM.SW UPLOAD
BUSY-“
SubRemocon display “----STARTUP BUSY----“ (if
present)
Action Result