4. Motion Control Instructions
4-216 DVP-MC operating manual
3. Stop
If the coordinate motion instruction is being executed, set “Stop” to ON and the execution of the
corresponding coordinate motion instruction will be stopped at the deceleration in the coordinate
motion instruction and the state of each axis is Standstill.
If the coordinate motion instruction is executed again, reset “Stop” and then execute DNC_Group
instruction again. Please note that the current position of each axis must be consistent with the
terminal position of the coordinate motion instruction to be executed when coordinate motion
instruction is executed again. If the instruction to be executed is the circular instruction, consider if the
current point, the terminal point of arc, center of a circle or radius can make up a circular arc in case of
any abnormality.
4. ManualMode
After “Manualmode” is started up, the running speed of the corresponding coordinate motion
instruction comes from the parameter setting of manual velocity. When “ManualMode” is off, the
execution of the G code, which has not been completed can continue at the speed and acceleration
set in the original instruction. The source of manual speed can be a constant or some register.