SiBE37-701_B Refrigerant Flow for Each Operation Mode
Refrigerant Circuit 100
Operation of refrigerant regulator
1. Recovery of refrigerant
Surplus refrigerant is recovered to refrigerant regulator by opening of SVL and SVG when
the indoor unit load is small.
2. Discharge of refrigerant
Discharge refrigerant from refrigerant regulator by opening of SVC when the load of the
outdoor unit is large.
3. Pressure regulating valve (Refrigerant regulator)
The circuit will be closed when SVL, SVO, SVG are all closed. In this case, the increased
pressure in the refrigerant regulator will be transferred to the liquid refrigerant pipe side, to
regulate the pressure.