Daikin REYQ16PY1B [314/477] Outdoor unit abnormal outdoor fan motor signal

Daikin REYQ16PY1B [314/477] Outdoor unit abnormal outdoor fan motor signal
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
303 Troubleshooting
3.26
H7
Outdoor Unit: Abnormal Outdoor Fan Motor Signal
Remote
Controller
Display
H7
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detection of abnormal signal from fan motor.
Malfunction
Decision
Conditions
In case of detection of abnormal signal at starting fan motor.
Supposed
Causes
Abnormal fan motor signal (circuit malfunction)
Broken, short circuited or disconnection connector of fan motor connection cable
Fan Inverter PCB malfunction (A2P)