SiBE37-701_B Specifications
Specifications 44
Concealed Ceiling Unit
1-1 TECHNICAL SPECIFICATIONS FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE
Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6
Heating kW 2.5 3.2 4.0 5.0 6.3
Power Input
(50Hz)
Cooling kW 0.081 0.081 0.085 0.194 0.215
Heating kW 0.069 0.069 0.073 0.182 0.203
Casing Material Galvanised steel plate
Dimensions Unit Height mm 300
Width mm 550 550 550 700 1,000
Depth mm 700
Weight Unit kg 25 25 25 28 36
Heat
Exchanger
Dimensions
Nr of Rows 3
Fin Pitch mm 1.75
Face Area 0.098 0.098 0.098 0.148 0.249
Nr of Stages 16
Fan Type Sirocco fan
Airflow Rate Cooling High high m³/min 9 9 9 16 18
High m³/min 7.5 7.5 8 13 16.5
Low m³/min 6.5 6.5 7 11 15
Fan External
static
pressure
High Pa 100 100 100 160 200
Standard Pa 50 100
Low Pa 30 30 30 30 50
Motor Output
(high)
W 90 90 90 140 350
Drive Direct drive
Piping
connections
Liquid
(OD)
Type Flare connection
Diameter mm 6.35 6.35 6.35 6.35 6.35
Gas Type Flare connection
Diameter mm 12.7 12.7 12.7 12.7 12.7
Drain Diameter mm VP25 (I.D. 32/O.D. 25)
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Fan driver overload protector
Standard Accessories Operation manual
Installation manual
Drain hose
Sealing pads
Clamps
Washer
Screws
Insulation for fitting
Clamp metal
Air discharge flange
Air suction flange
Notes Nominal cooling capacities are based on following conditions: return air temperature: 27°CDB/19°CWB; outdoor
temperature: 35°CDB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Nominal heating capacities are based on following conditions: return air temperature: 20°CDB; outdoor temperature:
7°CDB/6°CWB; standard external static pressure: 100Pa; equivalent refrigerant piping: 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
External static pressure is changeable in 7, 18, 14, 10 stages within the ( ) range by the remote control.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric
method (gravity method) 50% or more.