Daikin REYQ16PY1B [240/477] Setting of refrigerant recovery mode

Daikin REYQ16PY1B [240/477] Setting of refrigerant recovery mode
Field Setting SiBE37-701_B
229 Test Operation
3.2.6 Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective electronic
expansion valve of indoor and outdoor units.
All indoor and outdoor unit’s operation are prohibited.
[Operation procedure]
c
In setting mode 2 with units in stop mode, set “Refrigerant Recovery / Vacuuming mode” to
ON. The respective electronic expansion valve of indoor and outdoor units are fully opened.
(H2P turns to display “TEST OPERATION” (blinks), “TEST OPERATION” and “UNDER
CENTRALIZED CONTROL” are displayed on the remote controller, and the all indoor /
outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of refrigerant recovery
operation.
d
Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detail.)
e
Press Mode button “BS1” once and reset “Setting Mode 2”.