SiBE37-701_B Specifications
Specifications 52
Wall Mounted Unit
1-2 ELECTRICAL SPECIFICATIONS FXAQ20PV1 FXAQ25PV1 FXAQ32PV1 FXAQ40PV1 FXAQ50PV1 FXAQ63PV1
Power
Supply
Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps
(MCA)
A 0.3 0.4 0.4 0.4 0.4 0.6
Maximum fuse amps
(MFA)
A15
Full load amps (FLA) A 0.2 0.3 0.3 0.3 0.3 0.5
Voltage
range
Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA is smaller than or equal to 4 × FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker