Daikin REYQ16PY1B [62/477] Wall mounted unit

Daikin REYQ16PY1B [62/477] Wall mounted unit
Specifications SiBE37-701_B
51 Specifications
Wall Mounted Unit
1-1 TECHNICAL SPECIFICATIONS FXAQ20PV1 FXAQ25PV1 FXAQ32PV1 FXAQ40PV1 FXAQ50PV1 FXAQ63PV1
Capacity Cooling kW 2.2 2.8 3.6 4.5 5.6 7.1
Heating kW 2.5 3.2 4.0 5.0 6.3 8.0
Power Input
(50Hz)
Cooling kW 0.016 0.022 0.027 0.020 0.027 0.050
Heating kW 0.024 0.027 0.032 0.020 0.032 0.060
Power Input
(60Hz)
Cooling kW 0.016 0.022 0.027 0.020 0.027 0.050
Heating kW 0.024 0.027 0.032 0.020 0.032 0.060
Casing Colour white (3.0Y8.5/0.5)
Dimensions Unit Height mm 290
Width mm 795 795 795 1,050 1,050 1,050
Depth mm 238
Weight Unit kg 11 11 11 14 14 14
Heat
Exchanger
Dimensions
Nr of Rows 2
Fin Pitch mm 1.40
Face Area 0.161 0.161 0.161 0.213 0.213 0.213
Nr of Stages 14
Fan Type Cross flow fan
Quantity 1
Cooling High m³/min 7.5 8 8.5 12 15 19
Low m³/min 4.5 5 5.5 9 12 14
Fan Motor Quantity 1
Model QCL9661M QCL9661M QCL9661M QCL9686M QCL9686M QCL9686M
Output
(high)
W404040434343
Drive Direct drive
Refrigerant Name R-410A
Cooling Sound
Pressure
High dBA 36.0 37.0 38.0 40.0 43.0 47.0
Low dBA 31.0 31.0 31.0 36.0 38.0 41.0
Piping
connections
Liquid
(OD)
Type Flare connection
Diameter mm 6.35 6.35 6.35 6.35 6.35 9.52
Gas Type Flare connection
Diameter mm 12.7 12.7 12.7 12.7 12.7 15.9
Drain Diameter mm VP13 (I.D. 13/O.D. 18)
Heat Insulation Foamed polystyrene/foamed polyethylene
Air Filter Washable resin net
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices PCB fuse
Standard Accessories Installation and operation manual
Installation panel
Paper pattern for installation
Insulation tape
Clamps
Screws
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Содержание