Daikin REYQ16PY1B [428/477] Fxzq20m 25m 32m 40m 50m9v1b

Daikin REYQ16PY1B [428/477] Fxzq20m 25m 32m 40m 50m9v1b
Wiring Diagrams for Reference SiBE37-701_B
417 Appendix
FXZQ20M / 25M / 32M / 40M / 50M9V1B
20, 25, 32, 40, 50 CLASS
(22, 28, 36, 45, 56 CLASS)
POWER SUPPLY
220-240V
~
50Hz
F2U
Q1DI
L
N
MAX. 300
A1P A3P A4P
X23A X2A
X1A
SS1
SS2
(SEE NOTE 3)
H1P
H2P
H3P
H4P
X1A
BS1
L
N
X2M
RED
WHT
GRN/YLW
S1L
M
Y1E
X31A
X8A
F1U
R1T
R2T
X13A X12A X11A
R3T
X1A
T1R
KPR
X11A
X25A
X7A
YLW
YLW
M1P
M
X16A X18A HAP
X28A
X4A
V1TR
X30A
X23A
(SEE
NOTE 3)
A1P
PNK
WHT
YLW
ORG
BLU
BLK
T2
T1
F2
F1
P2
P1
X1M
RED
BLK
MSW
M1S
INPUT FROM OUTSIDE
(SEE NOTE 4)
TRANSMISSION WIRING CENTRAL
REMOTE CONTROLLER (SEE NOTE 2)
P2
P1
R1T
SS1
WIRED REMOTE
CONTROLLER
Q1M
M1F
M
C1
WHT
YLW
SWITCH BOX
X1M
A1P
C1
T1R
X2M
B
A1P PRINTED CIRCUIT BOARD T1R TRANSFORMER (220-240V/22V)
H3P
LIGHT EMITTING DIODE
(FILTER SIGN-RED)
C1 CAPACITOR (M1F) V1TR TRIAC
F1U FUSE ((B), 5A, 250V) X1M TERMINAL STRIP
H4P
LIGHT EMITTING DIODE
(DEFROST-ORANGE)
F2U FIELD FUSE X2M TERMINAL STRIP
HAP
LIGHT EMITTING DIODE (SERVICE
MONITOR GREEN)
Y1E ELECTRONIC EXPANSION VALVE SS1 SELECTOR SWITCH (MAIN/SUB)
WIRED REMOTE CONTROLLER
SS2
SELECTOR SWITCH
(WIRELESS ADDRESS SET)
KPR MAGNETIC RELAY (M1P) R1T THERMISTOR (AIR)
M1F MOTOR (INDOOR FAN) SS1 SELECTOR SWITCH (MAIN/SUB) CONNECTOR FOR OPTIONAL PARTS
M1P MOTOR (DRAIN PUMP)
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
X16A
CONNECTOR
(ADAPTOR FOR WIRE)
M1S MOTOR (SWING FLAP)
Q1DI
FIELD EARTH LEAK DETECTOR
(MAX. 300mA)
A3P PRINTED CIRCUIT BOARD
X18A
CONNECTOR (ON/OFF)
(WIRING ADAPTOR FOR
ELECTRICAL APPENDICES)
A4P PRINTED CIRCUIT BOARD
Q1M
THERMAL PROTECTOR
(M1F EMBEDDED)
BS1 PUSH BUTTON (ON/OFF)
H1P
LIGHT EMITTING DIODE
(ON-RED)
RED:RED PNK:PINK
BLK:BLACK ORG:ORANGE
WHT:WHITE GRN:GREEN
YLW:YELLOW BLU:BLUE
R1T THERMISTOR (AIR)
R2T THERMISTOR (COIL-LIQUID)
H2P
LIGHT EMITTING DIODE
(TIMER-GREEN)
R3T THERMISTOR (COIL-GAS)
S1L FLOAT SWITCH
:
TERMINAL
: CONNECTOR
: WIRE CLAMP
: FIELD WIRING
NOTES:
1. IN CASE OF USING A REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE TO THE ATTACHED INSTALLATION MANUAL.
2. X23A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.
3. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED TO THE UNIT.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM.
SEE TECHNICAL DATA AND CATALOGS, ETC. BEFORE CONNECTION.
3TW26426-1C

Содержание

Скачать