Daikin REYQ16PY1B [429/477] 25 32 63 class

Daikin REYQ16PY1B [429/477] 25 32 63 class
SiBE37-701_B Wiring Diagrams for Reference
Appendix 418
FXCQ20M / 25M / 32M / 63M8V3B
C1R
T1R
X2M X1M
A1P
SWITCH BOX
1N~50Hz 230V
LN
Q2E
F2U
X1M
LN
RED
BLU
A1P
F1U
T1R
X3A
X1A
X4A
FC FH FL FLL
L
N
X13A X12A X11A X9A X8A
X18A
T2
T1
F2
F1
P2
P1
X23A
Y1Y2X7A
HAP
RyP
RyA
RyF3
RyF2
RyF1
X6A
R1T R2T R3T
33S 33H
indoor
20,25,32,63 CLASS
(22,28,36,71 CLASS)
PNK
WHT
YLW
ORG
BLU
BLK
T2
T1
F2
F1
P2
P1
X2M
INPUT FROM
OUTSIDE (Note 3)
TO CENTRAL REMOTE
CONTROLLER (Note 1)
WIRED REMOTE
CONTROLLER
(Note 2)
P2
P1
RED
BLK
ORG
BRN
M1F
M
1
WHT
YLW
C1R
M
1
M
M
1
M1S Y1E M1P
A1P A2P
SS1
SS2
X2A
X23A
X1A
A3P
H1P
H2P
H3P
H4P
X1A
BS
NOTE 2 RECEIVER / DISPLAY UNIT
COLORS:
BLK : BLACK
BLU : BLUE
BRN : BROWN
ORG : ORANGE
PNK : PINK
RED : RED
WHT : WHITE
YLW : YELLOW
FIELD WIRING
: LIVE
: NEUTRAL
: CONNECTOR
: WIRE CLAMP
: PROTECTIVE
EARTH (SCREW)
L
N
33H FLOAT SWITCH R2T, R3T THERMISTOR (COIL) H1P LIGHT EMITTING DIODE (ON-RED)
33S LIMIT SWITCH (SWING FLAP) Q2E EARTH LEAK DETECTOR H2P LIGHT EMITTING DIODE (TIMER-GREEN)
A1P PRINTED CIRCUIT BOARD RyA MAGNETIC RELAY (M1S) H3P LIGHT EMITTING DIODE (FILTER SIGN-RED)
C1R CAPACITOR (M1F) RyF1-3 MAGNETIC RELAY (M1F) H4P LIGHT EMITTING DIODE (DEFROST-ORANGE)
F1T THERMAL FUSE (152°C) (M1F EMBEDDED) RyP MAGNETIC RELAY (M1P) SS1 SELECTOR SWITCH (MAIN/SUB)
F1U FUSE (250V, 5A) T1R TRANSFORMER (220-240V/22V) SS2
SELECTOR SWITCH (WIRELESS ADDRESS SET)
F2U FIELD FUSE X1M TERMINAL STRIP (POWER) CONNECTOR FOR OPTIONAL PARTS
HAP
LIGHT EMITTING DIODE
(SERVICE MONITOR-GREEN)
X2M TERMINAL STRIP (CONTROL)
X18A
CONNECTOR (WIRING, ADAPTOR FOR
ELECTRICAL APPENDICES)
Y1E ELECTRONIC EXPANSION VALVE
M1F MOTOR (INDOOR FAN)
RECEIVER/DISPLAY UNIT (ATTACHED TO WIRELESS
REMOTE CONTROLLER)
X23A
CONNECTOR (WIRELESS REMOTE CONTROLLER)
M1S MOTOR (SWING FLAP)
M1P MOTOR (DRAIN PUMP) A2P, A3P PRINTED CIRCUIT BOARD
R1T THERMISTOR (AIR) BS ON/OFF BUTTON
NOTES:
1. WHEN USING A CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.
2. X23A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS USED.
3. WHEN CONNECTING THE INPUT WIRES FROM THE OUTDOOR UNIT, "FORCED OFF" OR "ON/OFF" OPERATION CAN BE SELECTED BY THE REMOTE CONTROLLER.
FOR MORE DETAILS SEE INSTALLATION MANUAL.
4. USE COPPER CONDUCTORS ONLY.
2TW23776-1D