Test Operation SiBE37-701_B
185 Test Operation
Setting the mode
The set mode can be changed with the button according to the following procedure:
For setting mode 1: Press the button once, the H1P LED is off
h
. This mode is
not available for heat recovery units.
For setting mode 2: Press the button for 5 seconds, the H1P LED is on
k
.
If the H1P LED is blinking l
and the button is pushed once, the setting mode will
change to setting mode 1.
Note: If you get confused in the middle of the setting process, push the button. Then it
returns to setting mode 1 (H1P LED is off).
Setting mode 2
The H1P LED is on.
Setting procedure
1. Push the button according to the required function (A~H). The LED indication that
matches the required function is shown below in the field marked :
2. When the button is pushed, the current setting is defined.
3. Push the button according to the required setting possibility as shown below in the
field marked.
3.1Possible settings for function A, B, F, and G are (ON) or (OFF).
(a) This setting = factory setting
BS1 MODE
BS1 MODE
BS1 MODE
BS1 MODE
BS1 MODE
Possible functions
A additional refrigerant charging operation.
B refrigerant recovery operation/vacuuming operation.
C automatic low noise operation setting at nighttime.
D low noise operation level setting ( ) via the external control adaptor.
E power consumption limitation setting ( ) via the external control adaptor.
F enabling function of the low noise operation level setting ( ) and/or power consumption
limitation setting ( ) via the external control adaptor (DTA104A61/62).
G high static pressure setting
H evaporating temperature setting
H1P H2P H3P H4P H5P H6P H7P
A
k h k h k h h
B
k h k h k h k
C
k h k h k k h
D
k h k k h h k
E
k h k k k k h
F
k h h k k h h
G
k h k h h k h
H
k h h k h h h
H1P H2P H3P H4P H5P H6P H7P
khhhhl h
(a)
khhhhh l
BS2 SET
L.N.O.P
DEMAND
L.N.O.P
DEMAND
BS3 RETURN
BS2 SET
ON
OFF
ON
OFF