Daikin REYQ16PY1B [64/477] Floor standing unit

Daikin REYQ16PY1B [64/477] Floor standing unit
Specifications SiBE37-701_B
53 Specifications
Floor Standing Unit
1-1 TECHNICAL SPECIFICATIONS FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE
Nominal
Capacity
Cooling kW 2.20 2.80 3.60 4.50 5.60 7.10
Heating kW 2.50 3.20 4.00 5.00 6.30 8.00
Power input
(50Hz)
Cooling kW 0.049 0.049 0.090 0.090 0.110 0.110
Heating kW 0.049 0.049 0.090 0.090 0.110 0.110
Power input
(60Hz)
Cooling kW 0.0.047 0.047 0.079 0.084 0.105 0.108
Heating kW 0.047 0.047 0.079 0.084 0.105 0.108
Casing Colour Ivory white (5Y7,5/1)
Dimensions Unit Height mm 600 600 600 600 600 600
Width mm 1000 1000 1140 1140 1420 1420
Depth mm 222 222 222 222 222 222
Weight Unit kg 25 25 30 30 36 36
Heat
Exchanger
Dimensions
Nr of Rows 333333
Fin Pitch mm 1.50 1.50 1.50 1.50 1.50 1.50
Face Area 0.159 0.159 0.200 0.200 0.282 0.282
Nr of Stages 14 14 14 14 14 14
Fan Type Sirocco fan
Quantity 111111
Airflow Rate Cooling High m³/min 7.00 7.00 8.00 11.00 14.00 16.00
Low m³/min 6.00 6.00 6.00 8.50 11.00 12.00
Fan Motor Quantity 111111
Model D14B20 D14B20 2D14B13 2D14B13 2D14B20 2D14B20
Output
(high)
W151525253535
Drive Direct drive
Refrigerant Name R-410A
Cooling Sound
Pressure
High dBA 35.0 35.0 35.0 38.0 39.0 40.0
Low dBA 32.0 32.0 32.0 33.0 34.0 35.0
Piping
connections
Liquid
(OD)
Type Flare connection
Diameter mm 6.4 6.4 6.4 6.4 6.4 9.5
Gas Type Flare connection
Diameter mm 12.7 12.7 12.7 12.7 12.7 15.9
Drain Diameter mm O.D. 21
Heat Insulation Glass Fiber/Urethane Foam
Air Filter Resin net with mold resistance
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices PCB fuse
Fan motor thermal protector
Standard
Accessories
Standard Accessories Installation and operation manual
Insulation for fitting
Drain hose
Clamps
Screws
Level adjustment screw
Washer
Notes Nominal cooling capacities are based on : indoor temperature : 27
°
CDB, 19
°
CWB, outdoor temperature : 35
°
CDB,
equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20
°
CDB, outdoor temperature : 7
°
CDB, 6
°
CWB,
equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Sound pressure levels are measured at 220V

Содержание

Скачать