Troubleshooting by Indication on the Remote Controller SiBE37-701_B
269 Troubleshooting
3.5
A7
Indoor Unit: Malfunction of Swing Flap Motor (M1S)
Remote
Controller
Display
A7
Applicable
Models
FXCQ, FXHQ, FXKQ
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing
flap motor is energized for a specified amount of time (about 30 seconds).
Error code is displayed but the system operates continuously.
Supposed
Causes
Defect of swing motor
Defect of connection cable (power supply and limit switch)
Defect of airflow direction adjusting flap-cam
Defect of indoor unit PCB