Daikin REYQ16PY1B [341/477] Outdoor unit malfunction of transmission between inverter and control pcb

Daikin REYQ14PY1B [341/477] Outdoor unit malfunction of transmission between inverter and control pcb
SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 330
3.43
LC
Outdoor Unit: Malfunction of Transmission between
Inverter and Control PCB
Remote
Controller
Display
LC
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
Malfunction of connection between the inverter PCB and outdoor main PCB
Defect of outdoor main PCB (transmission section)
Defect of inverter PCB
Defect of noise filter
Faulty fan inverter
Incorrect type of inverter PCB
Faulty inverter compressor
Faulty fan motor
External factor (noise etc.)