Wiring Diagrams for Reference SiBE37-701_B
413 Appendix
2.2 Field Wiring
REYQ8P / 10P / 12P / 14P / 16PY1B
POWER SUPPLY
L1 L2L3 N
SWITCH
FUSE
L1 L2 L3 N
OUTDOOR UNITS
Notes1) All wiring, components and materials to be procured
on the site must comply with the applicable local and
national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by
licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power sources in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
power goes on and off while the product is operating, attach a reversed phase protection
circuit locally.
Running the product in reversed phase may break the compressor and other parts.
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE)
(TRANSMISSION LINE)
(TRANSMISSION LINE)
SWITCH
FUSE
LN
2 WIRES CABLE
(POWER LINE)
SWITCH
(POWER LINE)
FUSE
LN
2 WIRES CABLE
BS UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
SWITCH
FUSE
LN
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
SWITCH
FUSE
LN
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
2 WIRES CABLE
(POWER LINE)
SWITCH
FUSE
LN
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
LN
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
LN
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
COOLING ONLY UNIT
LN
3D057764A
MAIN SWITCH