Daikin REYQ16PY1B [350/477] Outdoor unit refrigerant shortage alert

Daikin REYQ16PY1B [350/477] Outdoor unit refrigerant shortage alert
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
339 Troubleshooting
3.47
U0
Outdoor Unit: Refrigerant Shortage Alert
Remote
Controller
Display
U0
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect refrigerant shortage based on the temperature difference between low pressure or
suction pipe
and heat exchanger.
Malfunction
Decision
Conditions
[In cooling mode]
Low pressure becomes 0.1MPa or below.
[In heating mode]
The degree of superheat of suction gas becomes 20 degrees and over.
SH= Ts1 –Te
Ts1: Suction pipe temperature detected by thermistor
Te : Saturated temperature corresponding to low pressure
Malfunction is not determined. The unit continues the operation.
Supposed
Causes
Refrigerant shortage or refrigerant clogging (piping error)
Defective thermistor (R4T, R7T, R12T, R15T)
Defective low pressure sensor
Defective outdoor unit PCB (A1P)