Daikin REYQ16PY1B [307/477] Outdoor unit malfunction of electronic expansion valve coil y1e y5e

Daikin REYQ16PY1B [307/477] Outdoor unit malfunction of electronic expansion valve coil y1e y5e
SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 296
3.22
E9
Outdoor Unit: Malfunction of Electronic Expansion
Valve Coil (Y1E~Y5E)
Remote
Controller
Display
E9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of electronic expansion valve
Malfunction
Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E)
Defect of electronic expansion valve coil
Defect of outdoor unit main PCB (A1P)