SiBE37-701_B Field Setting
Test Operation 200
(14) Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory setting to “01.”
Setting Table
(15) Operation of Downward Flow Flap: Yes/No
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
(16) Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Setting Table
Some indoor unit models are not equipped with draft prevention (upward) function.
(17) Setting of the Static Pressure Selection (for FXDQ model)
Mode No. First Code No.
Second Code
No.
Setting
13 (23) 1
01 F : 4-direction airflow
02 T : 3-direction airflow
03 W : 2-direction airflow
Mode No. First Code No. Second Code No. Setting
13 (23) 3
01 Down-flow operation: Yes
02 Down-flow operation: No
(S2537)
Mode No. First Code No. Second Code No. Setting
13 (23) 4
01
Upward (Draft
prevention)
02 Standard
03
Downward (Ceiling
soiling prevention)
Model No. First Code No. Second Code No. External static pressure
13 (23) 5
01 Standard (15Pa)
02
High static pressure (44Pa)