Daikin REYQ16PY1B [431/477] Fxkq25ma 32ma 40ma 63mave

Daikin REYQ16PY1B [431/477] Fxkq25ma 32ma 40ma 63mave
SiBE37-701_B Wiring Diagrams for Reference
Appendix 420
FXKQ25MA / 32MA / 40MA / 63MAVE
INDOOR UNIT
A1P PRINTED CIRCUIT BOARD
A2P TERMINAL BOARD
C1 CAPACITOR (M1F)
F1U FUSE((B),5A, 250V)
HAP LIGHT EMITTING DIODE
(SERVICE MONITOR-GREEN)
K1R-K3R MAGNETIC RELAY (M1F)
KAR MAGNETIC RELAY (M1S)
KPR MAGNETIC RELAY (M1P)
M1F MOTOR (INDOOR FAN)
M1P MOTOR (DRAIN PUMP)
M1S MOTOR (SWING FLAP)
Q1M THERMO. SWITCH
(M1F EMBEDDED)
R1T THERMISTOR (AIR)
R2T·R3T THERMISTOR (COIL)
S1L FLOAT SWITCH
S1Q LIMIT SWITCH (SWING FLAP)
T1R TRANSFORMER (220-240V/22V)
X1M TERMINAL BLOCK (POWER)
X2M TERMINAL BLOCK (CONTROL)
Y1E ELECTRONIC EXPANSION VALVE
WIRED REMOTE CONTROLLER
R1T THERMISTOR (AIR)
SS1 SELECTOR SWITCH (MAIN/SUB)
CONNECTOR FOR OPTIONAL PARTS
X16A
CONNECTOR (ADAPTOR FOR WIRING)
X18A CONNECTOR (WIRING ADAPTOR
FOR ELECTRICAL APPENDICES)
NOTES) 1. : TERMINAL BLOCK, , : CONNECTOR, : TERMINAL
2. : FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO
THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL.
4. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF
CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
5. IN CASE HIGH E.S.P. OPERATION, CHANGE OVER THE WIRING CONNECTION FROM X2A TO X3A.
6. SYMBOLS SHOW AS FOLLOWS. (PNK : PINK WHT : WHITE YLW : YELLOW ORG : ORANGE BLU : BLUE
BLK : BLACK RED : RED BRN : BROWN GRY : GRAY)
7. USE COPPER CONDUCTORS ONLY.
NOTE-5
RED
GRY
BLK
ORG
BRN
X1A
X3A
YC
A2P
X4A
X2A
LL
BRN
ORG
BLKRED
FC FL FLL
220-240V
~
50Hz
220V
~
60HZ
POWER SUPPLY
X1M
A1P
F1U
X3A
T1R
X4A
X1A
A2P
YC
X1A
X3A
RED
GRY BLK
ORG BRN
WHT
C1
YLW
Q1M
M1F
M
~
X2A
LL
RED BLK
ORG
BRN
FC FH FL FLL X6A
K1R
K2R K3R
KAR KPR
Y2 Y1
LN
RED WHT
GRN/
YLW
LN
X13A X12A X11A X9A X8A
BLK
X16A
HAP
X18A
R1T
R2T
R3T
S1Q
S1L
X30A
T2
T1
F2
F1
P2
P1
X7A
MSW
~
M
~
M
M1P
M1S
Y1E
RED WHT
WHT
X2M
BLK
BLU
ORG
YLW
WHT
PNK
P1
P2
F1
F2
T1
T2
R1T
P1 P2
SS1
WIRED REMOTE CONTROLLER
(OPTIONAL ACCESSORY)
NOTE-3
TRANSMISSION
WIRING CENTRAL
REMOTE
CONTROLLER
NOTE-4
INPUT FROM OUTSIDE
ELECTRIC PARTS BOX
X18A X16A
A1P
T1R
A2P
X1M
C1
X2M
3D039564C
FH

Содержание

Скачать