Daikin REYQ16PY1B [159/477] When the float switch is tripped during heating operation

Daikin REYQ16PY1B [159/477] When the float switch is tripped during heating operation
SiBE37-701_B Outline of Control (Indoor Unit)
Function 148
6.3.3 When the Float Switch is Tripped During Heating Operation:
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.3.4 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Controller:
*4. (Malfunction residual):
If the float switch is tripped five times in succession, a drain malfunction is determined to
have occurred. “AF” is then displayed as operation continues.
*5. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop
if the float switch is OFF for more than 5 minutes in the case of *4.
Thermostat
(running)
Float switch
Drain pump
ON
OFF
OFF
ON
ON
OFF
5 min.
5 min.
5 sec.
Remote controller "A3" flashing malfunction stop
Humidifier
ON
OFF
Reset
Remote
controller
display
Drain pump
OFF
ON
"AF" display (running)
Float switch
OFF
ON
*1 : 5 min.
1st time 2nd time 3rd time 4th time 5th time
Enters malfunction treatment
if the float switch is not reset
within 5 minutes.
Remote controller "A3" flashing
malfunction stop
1
1
1
1
1
1
1
5 sec.
5
4
ON
OFF