Daikin REYQ16PY1B [244/477] Cancel disabling the compressor 1 on the right side from operating set no 38 disable compressor 1 operation of setting mode 2 to off

Daikin REYQ16PY1B [244/477] Cancel disabling the compressor 1 on the right side from operating set no 38 disable compressor 1 operation of setting mode 2 to off
Field Setting SiBE37-701_B
233 Test Operation
[Cancel of Emergency Operation]
To cancel the emergency operation, conduct the following setting. (Return to Factory setting.)
<REYQ8 to 16PY1>
k
Cancel disabling the compressor 1 (on the right side) from operating:
Set No. 38 "Disable-compressor-1 operation" of setting mode 2 to "OFF".
k
Cancel disabling the compressor 2 (on the left side) from operating:
Set No. 39 "Disable-compressor-2 operation" of setting mode 2 to "OFF".
<REYQ18 to 48PY1>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
*It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
k
Cancel disabling the outdoor unit 1 from operating:
Set No. 38 "Disable outdoor unit 1 operation" of setting mode 2 to "OFF".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
khhhhhh
(2) Press the OPERATE button (BS2) 38
times.
kkhhkkh
(3) Press the CHECK button (BS3) once.
khhhhlh
(4) Press the OPERATE button (BS2) once.
khhhhhl
(Factory setting)
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 39
times.
kkhhkkk
(3) Press the CHECK button (BS3) once.
khhhhlh
(4) Press the OPERATE button (BS2) once.
khhhhhl
(Factory setting)
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
hhkhhhh
k
Outdoor unit 2:
hhhhhhh
l
Outdoor unit 3:
hhhhhhh
h
(Factory setting)
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
khhhhhh
(2) Press the OPERATE button (BS2) 38
times.
kkhhkkh
(3) Press the CHECK button (BS3) once.
khhhhlh
(4) Press the OPERATE button (BS2) once.
khhhhhl
(Factory setting)
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh