Refrigerant Circuit SiBE37-701_B
61 Refrigerant Circuit
1.2 REYQ14P, 16P
No. in
refrigerant
system
diagram
Symbol Name Major Function
1 M1C Inverter compressor (INV1)
Inverter compressor is operated on frequencies between 52Hz and 266Hz by using
the inverter. The number of operating steps is as follows.
REYQ14P or 16P : 26 step
2M2C
Standard compressor 1 (
INV2
)
3 M1F Inverter fan
Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.
4 M2F Inverter fan
Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.
5(6)
Y1E
(Y3E)
Electronic expansion valve
(Main: EVM)
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
7(8)
Y2E
(Y5E)
Electronic expansion valve
(Subcooling: EVT)
PI control is applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
9Y4E
Electronic expansion valve
(Refrigerant charge: EVJ)
This is used to open/close refrigerant charge port.
10(11)
Y5S
(Y10S)
Solenoid valve (Main bypass: SVE)
This opens in cooling operation.
12 Y4S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
13 Y3S
Solenoid valve (Refrigerant
regulator liquid pipe: SVL)
This is used to collect refrigerant to the refrigerant regulator.
14 Y1S
Solenoid valve (Refrigerant
regulator gas vent pipe: SVG)
This is used to collect refrigerant to the refrigerant regulator.
15 Y7S
Solenoid valve (Refrigerant
regulator discharge pipe:
SVO)
This is used to discharge refrigerant from the refrigerant regulator.
16 Y6S
Solenoid valve (Discharge
pipe of refrigerant regulator)
Bypass the high pressure gas to the refrigerant regulator.
17(18)
Y2S
(Y9S)
Four way valve (Heat
exchanger switch: 20SA)
This is used to switch outdoor heat exchanger to evaporator or condenser.
19 Y8S
Four way valve (Dual pressure
gas pipe switch: 20SB)
This is used to switch dual pressure gas pipe to high pressure or low pressure.
20 S1NPH High pressure sensor Used to detect high pressure.
21 S2NPL Low pressure sensor Used to detect low pressure.
22(23)
S1PH
(S2PH)
High pressure switch (For INV
compressor)
This functions when pressure increases to stop operation and avoid high pressure
increase in the fault operation.
24
Pressure regulating valve
(Liquid pipe)
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
25
Pressure regulating valve
(Refrigerant regulator)
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
26 Subcooling heat exchanger Apply subcooling to liquid refrigerant.
27 Refrigerant regulator Surplus refrigerant is held according to the operation conditions.
28 Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
29 Capillary tube This is used to discharge refrigerant from the refrigerant regulator.
30 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature and others.
31(41)
R8T
(R10T)
Thermistor (Suction pipe: TsA)
Used to detect suction pipe temperature.
32 R31T
Thermistor (INV1 discharge
pipe: Tdi)
Used to detect discharge pipe temperature. Used for compressor temperature
protection control.
33 R32T
Thermistor (INV2 discharge
pipe: Tds1)
35(45)
R4T
(R12T)
Thermistor (Heat exchanger
deicer: Tb)
Used to detect liquid pipe temperature of air heat exchanger. Used to make
judgements on defrosting operation.
36(46)
R2T
(R11T)
Thermistor (Heat exchanger
gas pipe: Tg)
This detects temperature of gas pipe for air heat exchanger. Used to exercise the
constant control of superheated degree when an evaporator is used for outdoor unit
heat exchanging.
37(47)
R7T
(R15T)
Thermistor (Heat exchanger
liquid pipe: Tf)
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve. Used to make judgements on the recover or discharge
refrigerants to the refrigerant regulator.
38(48)
R5T
(R13T)
Thermistor (Subcooling heat
exchanger gas pipe: Tsh)
This detects temperature of gas pipe on the evaporator side for the subcooling heat
exchanger. Used to exercise the constant control of superheated degree at the outlet
of subcooled heat exchanger.
39 R6T
Thermistor (Subcooling heat
exchanger liquid pipe: Tl)
This detects temperature of liquid pipe between the main expansion valve and
subcooling heat exchanger.
40(50)
R9T
(R14T)
Thermistor (Liquid pipe: Tsc)
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.