SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 370
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Is electricity being
introduce for the first
time after installation
or after an indoor or
outdoor unit PCB has
been replaced?
Normal
YES
NO
NO
YES
YES
NO
YES
NO
YES
NO
Is indoor - outdoor
and outdoor - outdoor
unit transmission
wiring normal?
Push and hold the RESET
button on the outdoor unit
PCB for 5 seconds.
Does a malfunction
occur?
Disconnect the
outdoor-outdoor unit
transmission wiring to
create the one-
system status, and
then check whether or
not the system is
normal.
Does a “
UH
malfunction occur for
all indoor units in the
system?
Does a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor and
outdoor units?
After fixing the incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
The unit will not run for up to
12 minutes.
Normal
Mount the DIII-NET expander
adaptor.
Replace the indoor unit PCB.
Replace the outdoor unit PCB
(A1P or A3P).
1: Check the correct wiring “indoor-outdoor” and “outdoor-outdoor” by Installation Instruction.
2: What is Auto Address?
This is the address automatically assigned to indoor units and outdoor units after initial power supply upon
installation, or after executing rewiring (Keep pressing the RESET button for more than 4 seconds).