SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 294
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
Remove the foreign substances.
Check if any foreign
substances around
the fan.
12HP ~18HP class models have 2 fans.
Check electric motor (electric motor 1 or 2) corresponding
to malfunction code “E7” in the monitor mode of outdoor
unit PCB. (Refer to P.255~P.256 for how to check)
Check in the monitor mode
Cut the power supply OFF and wait for 10 minutes.
{
Fan motor 1: relay connector or X1A, X2A of compressor
inverter PCB.
{
Fan motor 2: relay connector or X1A, X2A of fan inverter
PCB.
Check the connection status of the connectors
Check if any
connector is
disconnected.
{
Fan motor 1: Both power supply wire and signal wire are all
white.
{
Fan motor 2: Both power supply wire and signal wire are
red in the PCB side and white in the motor side.
Check the color of relay connectors
Relay
connectors have
any connection
error.
A
Insert the connector.
Correct the connection of the relay
connectors.
YES
YES
NO
YES
NO
5HP
8HP
~
12HP
18HP
~
F1U R10
X4A
V1R
X2A
X1A
Z5C
5
X1A X2A
RDE
WHT
BLK
MS
3~
5
M1F
F1U R10
X4A
V1R
X2A
X1A
Z5C
5
X1A
X2A
RDE
WHT
BLK
MS
3~
5
M1F
F1U R10
X4A
V1R
X2A
X1A
Z9C
5
X3A
X4A
RDE
WHT
BLK
MS
3~
5
M2F
X51A X5A
X3A
X51A
RED
RED
WHT
RED
WHT