Daikin REYQ16PY1B [302/477] Troubleshooting

Daikin REYQ16PY1B [302/477] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
291 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Local factor
Open the stop valve.
NO
NO
YES
YES
YES
YES
NO
YES
NO
YES
NO
NO
YES
NO
NO
YES
Power OFF
Power ON
Replace the connecting wires and
ensure right connection of the
connector.
Check if the
stop valve is
open.
Check if the relay wires
to the compressor are
correct.
Ensure correct connection.
W
U
V
Ensure correct connection.
Check if the connection
of UVW phase order is
correct.
Check if the wiring has
any error in mistake for
inverter compressor.
Replace the compressor.
Check if the wiring is the
same as in the electric wiring
diagram.
The insulation resistance of
the compressor is low (not
more than 100k
).
The compressor coil
has disconnection of
wires.
Restart and check the
operation. Check if the
condition occurs again.
Check if the start
mode is in the high
differential pressure
(not less than 0.5
MPa).
Conclude the work
There is a possibility of defect of
pressure equalizing.
Check the refrigerant circuit.
Defect of pressure equalizing
Check the refrigerant circuit.
Remove the connection between the
compressor and inverter. Set the power
transistor check mode ON using “Setting
mode 2” of the outdoor unit PCB.
Measure the inverter output voltage
(*2).
Note: Measurement should be
made while the frequency is stable.
Check if the inverter
output voltage between 3
phases is within ± 5V.
Replace the inverter PCB.
Replace the inverter compressor.
*1: Pressure difference between high pressure and low pressure before starting.
*2: The quality of power transistors/ diode modules can be judged by executing (P.384).
Check 4
Power OFF
Power ON