SiBE37-701_B Basic Control
Function 118
2.6 Heat Exchanger Control
While in heating or cool/heat simultaneous operation, ensure target condensing and
evaporating temperature by changing over the air heat exchange of outdoor unit to the
evaporator or the condenser in response to loads.
[Single system]
[Multi outdoor unit system]
Outdoor unit
Left side
Condenser
Right side
Condenser
GR < -20GR > 25
Outdoor unit
Left side
Evaporator
Right side
Condenser
GR > 25
GR < -20
Outdoor unit
Left side
Evaporator
Right side
Outdoor unit
Left side
Evaporator
Right side
Evaporator
GR < -10GR > 15
Note 1. "GR" is a numeric value
representing the current
balanced condition and
calculated from target
condensing temperature,
target evaporating
temperature, current
condensing temperature,
and current evaporating
temperature.
A1
A2
A3
A4
Outdoor unit
123
Condenser Condenser Condenser
GR < -10GR > 15
Outdoor unit
123
Condenser Condenser Condenser
GR < -20GR > 25
Outdoor unit
123
Condenser Condenser
GR < -10GR > 15
Outdoor unit
123
Condenser Evaporator Evaporator
Note 1. "GR" is a numeric value representing the current balanced
condition and calculated from target condensing temperature,
target evaporating temperature, current condensing temperature,
and current evaporating temperature.
Note 2. On the system with two outdoor units, if there is no step for the
destination of transition, that step will be skipped.
B1
B2
B3
GR > 25
GR < -20
GR > 25
Outdoor unit
12 3
Evaporator
GR < -10GR > 15
Outdoor unit
123
Evaporator Evaporator
GR < -10GR > 15
Outdoor unit
123
Evaporator Evaporator Evaporator