SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 350
3.53
U7
Outdoor Unit: Transmission Failure (Across
Outdoor Units)
Remote
Controller
Display
U7
Applicable
Models
All outdoor unit models
Method of
Malfunction
Detection
Micro-computer checks if transmission between outdoor units.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error in connecting wires between outdoor unit and external control adaptor for
outdoor unit
Connection error in connecting wires across outdoor units
Setting error in switching cooling/ heating
Integrated address setting error for cooling/ heating
(function unit, external control adaptor for outdoor unit)
Defective outdoor unit PCB (A1P or A3P)
Defective external control adaptor for outdoor unit