Daikin REYQ16PY1B [243/477] Disabling the compressor 2 on the left side from operating set no 39 of setting mode 2 to disable compressor 2 operation

Daikin REYQ16PY1B [243/477] Disabling the compressor 2 on the left side from operating set no 39 of setting mode 2 to disable compressor 2 operation
SiBE37-701_B Field Setting
Test Operation 232
k
Disabling the compressor 2 (on the left side) from operating:
Set No. 39 of setting mode 2 to "Disable-compressor-2 operation".
<REYQ18 to 48PY1>
Make disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
* It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
k
Disabling the outdoor unit 1 to operate:
Set No. 38 of setting mode 2 to "Disable outdoor unit 1 operation".
k
Disabling the outdoor unit 2 from operating:
Set No. 39 of setting mode 2 to "Disable-outdoor-unit-2 operation".
k
Disabling the outdoor unit 3 from operating:
Set No. 40 of setting mode 2 to "Disable-outdoor-unit-1 operation".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 39
times.
kkhhkkk
(3) Press the CHECK button (BS3) once.
khhhhhl
(Factory setting)
(4) Press the OPERATE button (BS2) once.
khhhhlh
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
hhkhhhh
k
Outdoor unit 2:
hhhhhhh
l
Outdoor unit 3:
hhhhhhh
h
(Factory setting)
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
khhhhhh
(2) Press the OPERATE button (BS2) 38
times.
kkhhkkh
(3) Press the CHECK button (BS3) once.
khhhhhl
(Factory setting)
(4) Press the OPERATE button (BS2) once.
khhhhlh
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 39
times.
kkhhkkk
(3) Press the CHECK button (BS3) once.
khhhhhl
(Factory setting)
(4) Press the OPERATE button (BS2) once.
khhhhlh
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 40
times.
kkhkhhh
(3) Press the CHECK button (BS3) once.
khhhhhl
(Factory setting)
(4) Press the OPERATE button (BS2) once.
khhhhlh
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh

Содержание