Daikin REYQ16PY1B [338/477] Outdoor unit inverter compressor starting failure

Daikin REYQ16PY1B [338/477] Outdoor unit inverter compressor starting failure
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
327 Troubleshooting
3.42
L9
Outdoor Unit: Inverter Compressor Starting Failure
Remote
Controller
Display
L9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect the failure based on the signal waveform of the compressor.
Malfunction
Decision
Conditions
Starting the compressor does not complete.
Supposed
Causes
Failure to open the stop valve
Defective compressor
Wiring connection error to the compressor
Large pressure difference before starting the compressor
Defective inverter PCB