Field Setting SiBE37-701_B
197 Test Operation
3.1.6 Detailed Explanation of Setting Modes
(1) Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
(2) Ultra Long Life Filter Sign Setting
When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Setting Table
(3) Selection of Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and room temperature thermistor in remote controller.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the room
temperature thermistor in remote controller.
(4) "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
(5) Airflow Adjustment (AUTO)
External Static Pressure Settings
Make settings in either method (a) or method (b) as explained below.
(a) Use the airflow auto adjustment function to make settings.
Airflow auto adjustment: The volume of blow-off air is automatically adjusted to the rated
quantity.
(b) Select External Static Pressure with Remote Controller Check that 01 (OFF) is set for the
“SECOND CODE NO.” in “MODE NO. 21” for airflow adjustment on an indoor unit basis in
Table 4. The “SECOND CODE NO.” is set to 01 (OFF) at factory setting. Change the
“SECOND CODE NO.” as shown in Table according to the external static pressure of the
duct to be connected.
Filter Specs.
Setting
Standard Filter Long Life Filter Ultra Long Life Filter
Contamination Light 200 hrs. 2,500 hrs. 10,000 hrs.
Contamination Heavy 100 hrs. 1,250 hrs. 5,000 hrs.
Mode No. First Code No. Second Code No. Setting
10 (20) 1
01 Long Life Filter
02 Ultra Long Life Filter
Mode No. First Code No. Second Code No. Thermistor that controls room temperature
10 (20) 2
01
Room temperature thermistor in remote
controller and suction air thermistor for
indoor unit
02 Suction air thermistor for indoor unit
03
Room temperature thermistor in remote
controller
Mode No. First Code No. Second Code No. "Filter Cleaning" display
10 (20) 3
01 Display
02 No display
Mode No. First Code No. Second Code No. Airflow adjustment
11 (21) 7
01 OFF
02 Completion of airflow adjustment
03 Start of airflow adjustment