SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 332
Troubleshooting
Replace the noise
filter of the A3P.
A
YES
The fuse F400U of the A3P has
been molten down.
Disconnect the sensor connector
(X2A or X4A) from the fan motor,
and then turn ON the power supply.
Is any malfunction
code other than "
LC
"
displayed?
The micro-computer
normal monitor (green) of
the main PCB (A1P) is
blinking.
The micro-computer
normal monitor (green) of
the main PCB (A4P) is
blinking.
The LC malfunction
recurs.
NO
YES
NO
NO
NO
YES
YES
YES
NO
Take countermeasures
following the displayed
malfunction code.
Not the LC malfunction.
Check the malfunction
code again.
Replace the inverter
PCB (A4P).
*
If the replaced PCB has significant
damage, the compressor is probably
get faulty. In this case, carry out
inspections on the compressor
again.
Replace the main PCB
(A1P).
Continue operation.
(It is supposed that the
malfunction results
from causes such as
instantaneous power
failure.)
F400U