Daikin REYQ16PY1B [285/477] Indoor unit malfunction of electronic expansion valve coil

Daikin REYQ16PY1B [285/477] Indoor unit malfunction of electronic expansion valve coil
SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 274
A9
Indoor Unit: Malfunction of Electronic Expansion
Valve Coil
Remote
Controller
Display
A9
Applicable
Models
Indoor units except FXFQ models
Method of
Malfunction
Detection
Check coil condition of electronic expansion valve by using micro-computer.
Malfunction
Decision
Conditions
Pin input for electronic expansion valve coil is abnormal when initializing micro-computer.
Supposed
Causes
Defective drive of electronic expansion valve
Defective PCB of indoor unit
Defective relay cables

Содержание

Скачать