Daikin REYQ16PY1B [245/477] Cancel disabling the outdoor unit 2 from operating set no 39 disable outdoor unit 2 operation of setting mode 2 to off

Daikin REYQ16PY1B [245/477] Cancel disabling the outdoor unit 2 from operating set no 39 disable outdoor unit 2 operation of setting mode 2 to off
SiBE37-701_B Field Setting
Test Operation 234
k
Cancel disabling the outdoor unit 2 from operating:
Set No. 39 "Disable-outdoor-unit-2 operation" of setting mode 2 to "OFF".
k
Cancel disabling the outdoor unit 3 from operating:
Set No. 40 "Disable-outdoor-unit-3 operation" of setting mode 2 to "OFF".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 39
times.
kkhhkkk
(3) Press the CHECK button (BS3) once.
khhhhlh
(4) Press the OPERATE button (BS2) once.
khhhhhl
(Factory setting)
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step) H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
khhhhhh
(2) Press the OPERATE button (BS2) 40
times.
kkhkhhh
(3) Press the CHECK button (BS3) once.
khhhhlh
(4) Press the OPERATE button (BS2) once.
khhhhhl
(Factory setting)
(5) Press the CHECK button (BS3) twice.
khhhhhh
(6) Press the PAGE button (BS1) once.
hhkhhhh