Daikin REYQ16PY1B Сервис мануал онлайн [116/477] 549049

Daikin REYQ16PY1B Сервис мануал онлайн [116/477] 549049
Function General SiBE37-701_B
105 Function
Symbol
Electric symbol
Description or function
REYQ8~16P
REMQ8~16P
Ta R1T (A1P) R1T (A1P) Outdoor air temperature
TsA
R8T (Suction
pipe1)
R8T Suction pipe temperature
R10T
(Suction
pipe2)
Tb
R4T
(Deicer1)
R4T Heat exchanger outlet temperature at cooling
R12T
(Deicer2)
Tg
R2T (Gas
pipe1)
R2T Heat exchanger gas pipe temperature
R11T (Gas
pipe2)
Tf
R7T (Liquid
pipe1)
R7T
Temperature of liquid pipe between heat exchanger and main electronic expansion
valve
R15T (Liquid
pipe2)
Tsh
R5T (Gas
pipe1)
R5T Temperature detected with the subcooling heat exchanger outlet thermistor
R13T (Gas
pipe2)
Tl
R6T (Liquid
pipe1)
R6T Liquid pipe temperature detected with the liquid pipe thermistor
R14T (Liquid
pipe2)
Tsc R9T R9T Temperature of liquid pipe between liquid stop valve and subcooled heat exchanger
Tc High pressure equivalent saturation temperature
TcS Target temperature of Tc
Te Low pressure equivalent saturation temperature
TeS Target temperature of Te
Tfin
R1T (A4P) (A5P)
R1T (A3P) Radiation fin temperature
Tp Calculated value of compressor port temperature
Tdi R31T (R32T) R31T Discharge pipe temperature of inverter compressor
Tds R32T R32T, R33T Discharge pipe temperature of standard compressor

Содержание