ioLogik W5300 The ioAdmin Utility
3-28
The Active Tags Panel
When logged in as administrator, fill in the fixed IP address on the Active Tags panel to configure address and
port settings for Active OPC. The Active OPC Server Address may use either an IP address or a URL. The
default port number is 9900. The port number should be the same as the one set as the Active OPC Server’s
Active Tag Listen Port. After the OPC and channel tags have been configured, click Create Tags. The ioLogik
W5300 must be rebooted in order for the settings to take effect.
The Heartbeat Interval configures the period of time for the heartbeat signal to the AOPC server; this is used
to confirm the connection between an ioLogik device and the Active OPC server is live. If the heartbeat interval
is set and the network between the ioLogik and Active OPC server is down, the AOPC panel will detect the
heartbeat has stopped and will display BAD in the Quality column to indicate the loss of connectivity.
Setting the heartbeat interval to 0 disables it. When the heartbeat is disabled, the SysConnect tag on the
Active OPC server will always be 1, indicating that the AOPC server will not know if the connection state is live
or dead.