Field Setting SiBE37-701_B
219 Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
24
ENECUT test
operation (Domestic
Japan only)
khkkhhh
ENECUT output OFF
khhhhhk
ENECUT output forced ON
khhhhkh
25
Setting of external
low noise level
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00 (factory setting)
khhhhkh
About 24:00
khhhkhh
27
Night-time low noise
operation end setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00 (factory setting)
khhhkhh
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk
ON
khhhhkh
29
Capacity
precedence setting
khkkkhk
OFF
khhhhhk
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh
80 % demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk
Demand 1
khhhhkh
Demand 2
khhhkhh
38
Emergency
operation (Master
unit is inhibited to
operate.)
kkhhkkh
OFF
khhhhhk
Master unit operation: Inhibited
khhhhkh
39
Emergency
operation (Slave unit
1 is inhibited to
operate.)
kkhhkkk
OFF
khhhhhk
Slave unit 1 operation: Inhibited
khhhhkh
40
Emergency
operation (Slave unit
2 is inhibited to
operate.)
kkhkhhh
OFF
khhhhhk
Slave unit 2 operation: Inhibited
khhhhkh
41
Prevention of minute
heating operation by
heating thermostat
OFF unit or non-
heating-operation
unit
kkhkhhk
OFF
khhhhhh
Non-heating-operation unit
khhhhhk
Heating thermostat OFF unit
khhhhkh
Non-heating-operation + Thermostat OFF unit
khhhhkk
42
Setting of BS Cool-
Heat selection
control time
kkhkhkh
6 min.
khhhhhh
4 min.
khhhhhk
51
Master-slave set-up
for multi outdoor
units
kkkhhkk
Automatic judgment
khhhhhh
Master
khhhhhk
Slave 1
khhhhkh
Slave 2
khhhhkk
The numbers in the "No." column represent the number of times to press the SET (BS2) button.