Daikin REYQ16PY1B Сервис мануал онлайн [231/477] 549049

Daikin REYQ16PY1B Сервис мануал онлайн [231/477] 549049
SiBE37-701_B Field Setting
Test Operation 220
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
No. Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0 Various settings
lhhhhhh
Lower 4 digits
1 C/H unified address
lhhhhhk
Lower 6 digits
2 Low noise/demand address
lhhhhkh
3 Not used
lhhhhkk
4 AIRNET address
lhhhkhh
5
Number of connected indoor units
*1
lhhhkhk
6 Number of connected BS units *2
lhhhkkh
7
Number of connected zone units
(Fixed to "0")
lhhhkkk
8 Number of outdoor units *3
lhhkhhh
9 Number of BS units *4
lhhkhhk
Lower 4 digits:
upper
10 Number of BS units *4
lhhkhkh
Lower 4 digits:
lower
11 Number of zone units
lhhkhkk
Lower 6 digits
12 Number of terminal units *5
lhhkkhh
Lower 4 digits:
upper
13 Number of terminal units *5
lhhkkhk
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
lhhkkkh
Malfunction
code table
Refer page
255.
15
Contents of malfunction
(1 cycle before)
lhhkkkk
16
Contents of malfunction
(2 cycle before)
lhkhhhh
20 Contents of retry (the latest)
lhkhkhh
21 Contents of retry (1 cycle before)
lhkhkhk
22 Contents of retry (2 cycle before)
lhkhkkh
25
Number of multi connection
outdoor units
lhkkhhk
Lower 6 digits
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
* Push the MODE (BS1) button and
returns to “Setting mode 1”.
(V2765)

Содержание