Field Setting SiBE37-701_B
221 Test Operation
Setting item 0 Display contents of “Number of units for various settings”
EMG operation /
backup operation
setting
ON
lhhkhhh
OFF
lhhhhhh
Defrost select setting Short
lhhhkhh
Medium
lhhhlhh
Long
lhhhhhh
Te setting L
lhhhhhh
M
lhhhhlh
H ~
lhhhhkh
Tc setting L
lhhhhhh
M
lhhhhhl
H
lhhhhhk
Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
The No. 1 cool/heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
In
c
the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is
22.
The number of terminal blocks for No. 12 and 13 is expressed as
an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
In
d
the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary
number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
See the preceding page for a list of data, etc. for No. 0 - 25.
l h
l
h
l
l
h
16 4
1
32 8 2
l
h h h l h l
64 16
No.12 128 32
l
h h h l l h
4 1
No.13 8 2