ioLogik E2200 Series Using the Web Console
5-6
In Event Counter mode, the channel accepts limit or proximity switches and counts events according to the
ON/OFF status. When “Lo to Hi” is selected, the counter value increases when the attached switch is pushed.
When “Hi to Lo” is selected, the counter value increases when the switch is pushed and released.
By default, the Event Counter value will be reset to zero if power is disconnected. If you select Save Status on
Power Failure, the Event Counter value will be saved when power is disconnected. When power is
reconnected, the value will be as you left it. You can set Power On Setting to have counting resume
immediately.
DI channels that are in Event Counter mode can begin counting automatically when the ioLogik is powered on.
To activate this function, enable Power On Setting. If Power On Setting is not enabled, the channel will only
start counting events when specified by a Modbus command or Click&Go Logic rule.
You can control how an Event Counter channel behaves during a network disconnection with the Safe Status
Setting and the Host Connection Watchdog. With the Watchdog disabled, the Event Counter continues
counting events even when there is a network disconnection. With the Watchdog enabled, the Safe Status
Setting specifies whether the Event Counter continues or suspends counting when there is a network
disconnection. Counting will continue if Safe Status Setting is enabled; counting will be suspended if Safe
Status Setting is not enabled.
NOTE
The ioLogik E2210 does not support the Save Status function in the event of a power failure.
DO Channels
On the DO Channels page, you can view the status of each DO (digital output) channel. Only DIO channels
that are acting as DO channels will be displayed.